Type Inverter heat pump
Model name AOYG36KBTB AOYG45KBTB
Power supply 230 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Starting current A 13.0 18.6
Fan
Airflow rate
Cooling
m
3
/h
3,750 4,450
Heating 3,750 4,450
Type × Q'ty Propeller × 1
Motor output W 100 120
Sound pressure level *1
Cooling
dB (A)
55 57
Heating 55 57
Sound power level
Cooling
dB (A)
70 71
Heating 70 71
Heat exchanger type
Dimensions
(H × W × D)
mm
Main1: 756 × 905 × 18.19
Main2: 756 × 905 × 18.19
Main1: 966 × 905 × 18.19
Main2: 966 × 905 × 18.19
Sub: 966 × 543 × 18.19
Fin pitch 1.45
Rows × Stages 1 × 36 1 × 46
Pipe type Copper
Fin
Type (Material) Aluminum
Surface treatment Blue fin
Compressor
Type × Q'ty DC Twin rotary × 1
Motor output W 1,500 2,180
Refrigerant
Type (Global warming potential) R32 (675)
Factory charge g 1,900 2,700
Refrigerant oil
Type FW68D RmM68AF
Amount
cm
3
600 800
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
788 × 940 × 320 998 × 940 × 320
Gross 966 × 1,027 × 445 1,176 × 1,027 × 445
Weight
Net
kg
52 67
Gross 60 75
Connection pipe
Size
Liquid
mm (in)
Ø9.52 (Ø3/8)
Gas Ø15.88 (Ø5/8)
Method Flare
Pre-charge length
m
30
Max. length 50
Max. height difference 30
Operation range
Cooling
°C
-15 to 46
Heating -15 to 24
Drain hose
Material LDPE
Tip diameter mm Ø13.0 (I. D.), Ø16.0 to Ø16.7 (O. D.)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• This data is based on EN 14511 standard.
- 64 -
1. Specifications
OUTDOOR UNIT
AOYG18-45KBTB
OUTDOOR UNIT
AOYG18-45KBTB