EasyManuals Logo
Home>Fujitsu>Air Conditioner>ARXG30KMLA

Fujitsu ARXG30KMLA Service Instruction

Fujitsu ARXG30KMLA
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
1-3. Dry operation
The compressor rotation frequency shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
Compressor frequency range
Unit: rps
Model name Outdoor temperature zone Operating frequency
ARXG30KMLA
X zone 44
J zone 44
Y zone 0
ARXG36KMLA
X zone 44
J zone 44
Y zone 0
ARXG45KMLA
X zone 33
J zone 33
Y zone 0
Compressor control based on room temperature
Ts+0.5°C
Ts -1.5°C
Ts-0.5°C
Ts+1.5°C
X zone
J zone
Y zone
Room temperature drops
Room temperature rises
Ts: Set temperature
1-3. Dry operation - (01-4) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Other manuals for Fujitsu ARXG30KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG30KMLA and is the answer not in the manual?

Fujitsu ARXG30KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG30KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals