¢ Model: AOYG45KBTB
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Frequency VI
Frequency VII
Time 1
Time 2 Time 3
Time 4
Time 5
Time 6
Time 7
Frequency VIII
Time 8
Frequency IX
Frequency X
Time 9
Time 10
Normal operation
Frequency
(rps)
I II III IV V VI VII VIII IX X
41 46 51 57 60 72 81 91 100 110
Time (sec)
1 2 3 4 5 6 7 8 9 10
60 120 180 240 360 420 480 540 600 660
Special operation
Frequency
(rps)
I II III IV V VI VII VIII IX X
41 46 51 57 60 72 81 91 100 110
Time (sec)
1 2 3 4 5 6 7 8 9 10
120 185 245 305 605 665 725 785 845 1,000
NOTES:
Normal operation:
Cooling and dry mode
Below 3 hours from the compressor stop and the compressor thermistor ≥ 15 °C
After defrost operation
Other than when the compressor starts for the first time since the breaker turns on
Special operation:
Other than the normal operation condition
When the compressor starts for the first time since the breaker turns on
1-4. Compressor frequency at normal start-up
- (01-6) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Other manuals for Fujitsu ARXG30KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG30KMLA and is the answer not in the manual?

Fujitsu ARXG30KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG30KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals