Before the test run, refer to he figure and
check the following items.
Is the outdoor unit securely installed?
Have you performed gas leakage inspection?
(Connection joints of various pipes (flang connection, brazing))
Is the heat insulation done completely?
(Gas pipe, liquid pipe, drain hose extension on indoor unit side etc)
Is the water discharging from drain without any problems?
Are the cables connected correctly?
Are the cables as per specif cations?
Is the earth wire connected accurately?
Are there any obstacles blocking the suction gate, and outlet of
the indoor/outdoor units?
Have you filled the specified amount of refrigerant?
Are the stop valves of gas pipe and liquid pipe fully open?
Has the power been supplied to crankcase heater for more than 6 hours?
If there are problems, adjust immediately and recheck.
Be sure to configure test run settings only when the outdoor unit has stopped
operating.
Test run setting method (it can be performed in the following two ways)
Set with test run setting (refer to installation instructions manual of indoor unit
for further details) available in the remote control.
Cooling Operation” and Heating Operation” can be set using , SELECT button and
ENTER button available on the board of display unit.
(*Make sure to perform the first test run with cooling operation.)
Set as per the procedure given below.
Depending on the communication status between the indoor and outdoor units,
it may take several minutes for the system to start operating after settings for the
test run are complete.
After the test run settings are complete, the outdoor units and the connected
indoor units will start operating. Room temperature control will not activate during
test operation (continuous operation).
If a knocking sound can be heard in the liquid compression of the compressor,
stop the unit immediately and then energize the crank case heater for a sufficient
length of time before restarting the operation.
Setting method
OUTDOOR UNIT
TEST RUN
Turn on the power of the outdoor unit and enter standby mode.
(1)
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Press the ENTER button for more than 3 seconds.
(2)
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
Blink
Press the SELECT button,
LED of the test run mode Switched between "COOL" and "HEAT".
(3)
Cooling test mode
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
Blink
Heating test mode
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
Blink
After confirmin the operation mode, Press ENTER button.(4)
The display changes as follows, and Air conditioner starts operation.
Cooling test mode
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink
Heating test mode
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Blink Off Off On Off Off Off Off
Off Off Off On Off Off Off
Off Off OffOff Off Off
Off Off Off Off Off Off
Off Off Off Off Off Off
OffOn Off Off OffOff Off Off
OffOn Off OffOff Off Off Off
Press [ENTER] button.
(5)
Air conditioner stopped operation.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE (L1) (L2) (L3) (L4) (L5) (L6)
Check items during test run
Test run method
Is the outdoor unit making any abnormal noise or vibrating significantly?
Is the cold air or hot air blowing from indoor unit according to the operation
mode?
Check that the “ERROR” LED blinks.
If it has displayed, check the error content as per 12.2. described later.
Operate the unit according to the operating manual provided with the indoor
unit, and check that it is operating normally.
2013.03.05 16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARYG45LMLA and is the answer not in the manual?

Fujitsu ARYG45LMLA Specifications

General IconGeneral
TypeAir conditioner indoor unit
Ionizer-
Multi-splitYes
Product colorGray
Refrigerating mediumR410A
Air conditioner functionsCooling, Dehumidifying, Heating
Refrigerating medium weight3350 g
Cooling capacity in watts (max)13300 W
Cooling capacity in watts (min)4000 W
Heating capacity in watts (max)15500 W
Heating capacity in watts (min)4200 W
Cooling capacity in watts (nominal)12100 W
Cooling energy efficiency (EER, W/W)3.77
Heating energy efficiency (COP, W/W)3.68
Seasonal efficiency rating (cooling) (SEER)5.07
Seasonal efficiency rating (heating) (SCOP)3.5
Heating capacity in watts (nominal) (Colder heating season)- W
Current25 A
AC input voltage230 V
Current (cooling)21 A
AC input frequency50 Hz
Design load (cooling)12.1 kW
Annual energy consumption (cooling)- kWh
Design load (heating) (Warmer heating season)- kW
Design load (heating) (Average heating season)13.3 kW
Indoor unit typeDucted
Indoor unit depth620 mm
Indoor unit width1135 mm
Indoor unit height270 mm
Indoor unit weight40000 g
Indoor units quantity1
Cooling airflow (indoor unit)2100 m³/h
Indoor unit noise level (low speed)28 dB
Indoor unit noise level (high speed)42 dB
Wi-FiNo
Outdoor unit noise level- dB

Related product manuals