4-6. Swing operation
¢ Compact cassette type
• To select up/down airflow swing operation
When the swing signal is received, the horizontal louver starts to swing.
– Swinging range
• Cooling mode/dry mode/fan mode: 1 ↔ 4
• Heating mode: 1 ↔ 4
– When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either upper end or bottom end.
¢ Wall mounted type
• To select up/down airflow swing operation
When the swing signal is received, the horizontal louver starts to swing.
– Swinging range
• Cooling mode/dry mode/fan mode (1 to 3): 1 ↔ 4
• Heating mode/fan mode (4 to 6): 3 ↔ 6
– When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either upper end or bottom end.
• To select left/right airflow swing operation(for KMTB model only)
When the swing signal is received, the vertical louver starts to swing.
– Swinging range
• All mode: 1 ↔ 5
– When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either left end or right end.
• To select up/down and left/right airflow swing operation (for KMTB model only)
When the swing signal is received, the horizontal and the vertical louvers start to swing.
¢ Ceiling type
• To select up/down airflow swing operation
When the swing signal is received, the horizontal louver starts to swing.
– Swinging range
• Cooling mode/dry mode/fan mode: 1 ↔ 7
• Heating mode: 1 ↔ 7
– When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either upper end or bottom end.
¢
Floor type
• To select up/down airflow swing operation
When the swing signal is received, the horizontal louver starts to swing.
– Swinging range
• Cooling mode/dry mode/fan mode: 1 ↔ 5
• Heating mode: 1 ↔ 5
– When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either upper end or bottom end.
4-6. Swing operation
- (04-59) - 4. Louver control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS