H x W x D
MEASUREMENT
DIMENSIONS
Shipping / Net
WEIGHT
POWER SOURCE
Cooling
Heating
STARTING CURRENT
AIR CIRCULATION
FAN MOTOR
Upper fan
Lower fan
Upper fan
Lower fan
DISCRIMINATION
COOLING
HEATING
MODEL NAME AOYG36LATT AOYG45LATT AOYG54LATT
1,290 x 900 x 330 mm
113 kg / 104 kg
10.0 A 10.0 A
6,200 m3/h 6,900 m3/h
10.0 A
6,200 m3/h
6,200 m3/h 6,750 m3/h 6,900 m3/h
400 V, 50 Hz, 3 phase, 4 W
750 r.p.m.
MFE-54VVT
750 r.p.m. 840 r.p.m.
780 r.p.m.
750 r.p.m.
780 r.p.m. 780 r.p.m. 870 r.p.m.
800 r.p.m. 800 r.p.m.
850 r.p.m. 900 r.p.m.
ELECTRICAL DATA
TYPE
DISCRIMINATION
WEIGHT (with oil)
REFRIGERANT TYPE R410A
Hermetic type, Inverter, 4 poles,
3 phase, DC motor, Twin Rotary
DA422A3F-29ZAD
23.0 kg
PRECHARGED REFRIGERANT
3,450 g
COMPRESSOR AND REFRIGERANT
2012.06.13 1
MAX PIPE LENGTH (Total) 75 m
(Between Branch pipe and IU)
20 m
(Between Indoor units)
0.5 m
MAX PIPE HEIGHT (Between OU and IU)
30 m
Pipe length
30 m
3,450 g
FULL CHARGE
45 m
4,200 g
60 m 4,950 g
75 m 5,700 g
ADDITIONAL CHARGE
50 g/m
NOISE LEVEL
COOLING
HEATING
OUTDOOR UNIT
SPECIFICATIONS
51 dB 54 dB 55 dB
53 dB 54 dB 56 dB