6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Model: AOHG18KATA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
15 — — — 0.953 0.950
10 — — 0.983 0.968 0.966
7.5 — 0.988 0.987 0.972 0.970
5 0.992 0.992 0.991 0.976 0.974
0 1.000 1.000 0.999 0.984 0.982
Indoor unit is lower than
outdoor unit *
2
-5 1.000 1.000 0.999 0.984 0.982
-7.5 — 1.000 0.999 0.984 0.982
-10 — — 0.999 0.984 0.982
-15 — — — 0.984 0.982
HEATING
Pipe length (m)
5 7.5 10 15 20
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
15 — — — 0.920 0.894
10 — — 0.982 0.920 0.894
7.5 — 1.000 0.982 0.920 0.894
5 1.000 1.000 0.982 0.920 0.894
0 1.000 1.000 0.982 0.920 0.894
Indoor unit is lower than
outdoor unit *
2
-5 0.995 0.995 0.977 0.916 0.889
-7.5 — 0.993 0.975 0.913 0.887
-10 — — 0.972 0.911 0.885
-15 — — — 0.902 0.876
- 82 -
6-1. Model: AOHG18KATA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG18-45KATA
OUTDOOR UNIT
AOHG18-45KATA