EasyManuals Logo
Home>Fujitsu>Air Conditioner>RSG12LMCA

Fujitsu RSG12LMCA User Manual

Fujitsu RSG12LMCA
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
23. OFF DEFROST OPEARTION CONTROL
01-19
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,
and then stop.
OFF Defrost Flow Chart
Heating operation stop
Defrost start
Defrost Indicater:
[Operation lamp]
7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature:
Over 16°C or
Compressor ON time: Over 15 minutes
Defrost end
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 16°C or
Compressor operation time has passed 15 minutes.
In heating operation, the outdoor heat exchanger temperature is less than - 4°C,
compressor continuous operation more than 10 minutes, and
compressor operation integrating time lasts for more than 30 minutes.
Outdoor heat exchanger temperature :
Below - 4°C
Compressor continuous operation :
Over 10 minutes
Compressor integrating operation :
Over 30 minutes

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu RSG12LMCA and is the answer not in the manual?

Fujitsu RSG12LMCA Specifications

General IconGeneral
BrandFujitsu
ModelRSG12LMCA
CategoryAir Conditioner
LanguageEnglish

Related product manuals