The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected
temperature by the indoor heat-exchanger sensor on heating mode.
( Fig.6 : Cool air prevension control )
01-06
6. COOL AIR PREVENTION CONTROL (Heating mode)
42°C
30°C
34°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
Hi
Me+
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7.
When the defrost operation starts, the indoor fan runs according to cool air preventtion control for 20 seconds.
And the fan is stopped if 20 seconds have passed.
When 60 seconds have passed after defrost operation is released,
the fan runs according to cool air preventtion control
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
9. DEFROST OPERATION
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.7.
It depends on the Function setting "Indoor unit fan control for energy saving".
8. INDOOR UNIT FAN (CONTROL FOR ENERGY SAVING (Cooling mode))
( Fig.7 : Indoor fan control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 7)
S-Lo
OFF
10 30 60 180 60 180 60 10 30
(sec)
( Table 7 : Indoor fan speed )
X zone J zone
07/09/12
680rpm 660rpm
680rpm
Dry
Cooling
42°C
30°C
34°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
Powerful
Hi
Lo
Cool air
prevention
39°C
37°C
37°C
32°C
28°C
S-Lo
<Normal operation>
<Powerful operation>
14
750rpm 730rpm 750rpm
Model