EasyManuals Logo
Home>GE>Air Conditioner>AEE09KP

GE AEE09KP User Manual

GE AEE09KP
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
59
Service Manual
Installation and Maintenance
The unit is
frequently ON/OFF
Power voltage is abnormal.
Heat-sinking capability of condenser
is not good. Neither is ventilation.
Too much refrigerant
Find out the cause and improve
power supply to stabilize the voltage.
Clean the condenser and clear the
blockage in front of air outlet.
Discharge the surplus refrigerant.
The unit operates
but cools
The set temperature is too high.
Refrigerant is inadequate or leaks
Cooling system is blocked.
Fan doesn’t operate or amount of
wind is inadequate.
Toomuch dust on filter
Compressor haslow efficiency.
Too much refrigerant
Relay of compressor doesn’t work
normally.
Turn down the temperature of thermostat.
Performleak test and ifthereis leakage, fix
it. Then supplement refrigerant according
torequirementafter vacuumization.
Check if thesystem is blockedby
observing evaporator and pressure
meter.
Checkif motor of fan is burnt out or if
the wiring is incorrect. If the motoris
burnt out, replace it.
Clean the filter.
Replace thecompressor.
Discharge thesurplus refrigerant.
Replace relay of compressor.
Indoor ambient termperature sensor is
short-cirtuited or open circuited.
Replace temperature sensor or related component.

Table of Contents

Other manuals for GE AEE09KP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE AEE09KP and is the answer not in the manual?

GE AEE09KP Specifications

General IconGeneral
BrandGE
ModelAEE09KP
CategoryAir Conditioner
LanguageEnglish

Related product manuals