• Output parameters
Output settings
Number of outputs 0 to 3
O u
Typ PROBE SCALE 4 DIGIT 3 DIGIT
TYPE + sign
Max Range Max Range
Sensor: Voltage
0 0...2V linear -1999/9999 -999/999
1 0...20V linear -1999/9999 -999/999
2 0...200V linear -1999/9999 -999/999
3 0...500V linear -1999/9999 -999/999
Sensor: Current
4 0...20mA linear -1999/9999 -999/999
5 0...50mA linear -1999/9999 -999/999
6 0...200mA linear -1999/9999 -999/999
7 0...1A linear -1999/9999 -999/999
8 0...5A linear -1999/9999 -999/999
0 None
1 Zero
2 Hold
3 Flash
4 Max. peak display
5 Min. peak display
6 Delta peak display
7 Peak memory reset
8 Zero + peak memory reset
9 Alarms reset
10 Peak + alarms reset
11 Zero + alarms reset
12 Peak + zero + alarms reset
13 Output status OUT1
14 Output status OUT2
15 Output status OUT3
d. i. - t. u. - t. d.
Offset correction of main
input
Select function of
digital input
High limit for the alarms
set point
-999 to 999
scale points
L.S ... H.S
Raise key function
(active only in
P.V.selection)
Low limit for the alarms
set point
L.S ... H.S
Lower key function
(active only in
P.V.selection)
Value Direct Absolute Normal
(max.) Relative to Symmetrical
Invers” previous (window)
(min.)
0 Direct Absolute Normal
1 Inverse Absolute Normal
2 Direct Relative Normal
3 Inverse Relative Normal
4 Direct Absolute Symmetrical
5 Inverse Absolute Symmetrical
6 Direct Relative Symmetrical
7 Inverse Relative Symmetrical
Alarm type 1
1. t - 2. t - 3. t
Alarm type 2
Alarm type 3
+8 to disable on power-up until first alarm
+16 to memorize
+32 to filter with F.O. mode (output filter mode)
min…max scale of input
selected in t.P
Maximum limit of main
input scale and analog
output
Decimal point position for
main input scale
dP Format
0 XXXX
1 XXX.X
2 XX.XX
3 X.XXX
Digital filter
on main input
Digital filter on process
variable display
0.0 to 20.0 sec
0.0 to 9.9 scale
points
Minimum limit of main
input scale and analog
output
min…max scale of input
selected in t.P
• AC input parameters
Input settings
Type of probe,
signal and scale of
main input
I n
-999 ... +999
scale points
• Information display
I F
Software version
Display of CPU type
(alternated) and number of
available outputs:
A3 = with 3 outputs
Information display
• Configuration parameters
C F
Hysteresis for set point 1
Hysteresis for set point 2
Hysteresis parameters
-999 ... +999
scale points
-999 ... +999
scale points
Hysteresis for set point 3
4