EasyManuals Logo
Home>Goodwe>Measuring Instruments>GM3000

Goodwe GM3000 User Manual

Goodwe GM3000
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
User Manual
Power Limit Solution for Grid-Tied PV Inverters
V1.0-2022-09-15
WARNING
1. Power o the equipment in the system before operations and maintenance. Otherwise, the equipment may be damaged or
electric shocks may occur.
2. The installation, electrical connection, and commissioning of the inverter, smart meter, communication box and other devices
in the system are not mentioned in this document. Please refer to the related user manual from the ocial website: https://
en.goodwe.com/
General Safety
System Safety
Matching Table
NOTICE
The information in this user manual is subject to change due to product updates or other reasons. This guide cannot replace
the product labels or the safety precautions in the user manual unless otherwise specied. All descriptions in the manual are for
guidance only.
Before installations, read through the corresponding user manual to learn about the product and the precautions. Strictly follow
its requirements.
All installations should be performed by trained and knowledgeable technicians who are familiar with local standards and safety
regulations.
Use insulating tools and wear personal protective equipment when operating the equipment to ensure personal safety. Wear
anti-static gloves, cloths, and wrist strips when touching electron devices to protect the inverter from damage.
Strictly follow the installation, operation, and conguration instructions in this manual. The manufacturer shall not be liable for
equipment damage or personal injury if you do not follow the instructions.
1 Safety Precaution
2 Networking
Product CT90 GM3000 HK3000 GM3000C SEC1000
DNS Series O × × × ×
XS Series O × × × ×
MS Series O × × × ×
NS Series O × × × ×
SDT G2 Series × O O O O
SMT Series × O O O O
MT Series × O × O O
HV 1100 Series × × × O O
Note The load current shall be
less than 90A.
The load current of each phase shall be
less than 120A.
The load current of any phase shall be more
than 120A.
For some inverter series, the power limit function is not available. Please contact After-sales Service if needed.
In networking systems with GM3000C + EzLogger Pro, or SEC1000, the power limit function can be fullled for multiple inverters
in parallel.
In networking systems with CT90, GM3000 or HK3000, it is only able to realize power limit function for single inverter.

Other manuals for Goodwe GM3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodwe GM3000 and is the answer not in the manual?

Goodwe GM3000 Specifications

General IconGeneral
BrandGoodwe
ModelGM3000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals