50
10 Technical Parameters
User Manual V1.0-2022-01-17
10 Technical Parameters
Technical Data GW4K-DT GW5K-DT GW6K-DT GW8K-DT
Input
Max.Input Power (W) 6000 7500 9000 12000
Max.Input Voltage(V) 1000 1000 1000 1000
MPPT Operating Voltage Range (V) 180~850 180~850 180~850 180~850
PV Input Operating Voltage
range(V)
160-1000 160-1000 160-1000 160-1000
Start-up Voltage (V) 160
Nominal Input Voltage (V) 620 620 620 620
Max. Input Current per MPPT (A) 12.5 / 12.5
Max. Short Circuit Current per
MPPT (A)
15.6 / 15.6
Max.Backfeed Current to The
Array(A)
0 0 0 0
Number of MPPT 2 2 2 2
Number of Strings per MPPT 1 1 1 1
Output
Nominal Output Power (W) 4000 5000 6000 8000
Nominal Output Apparent Power
(VA)
4000 5000 6000 8000
Max. AC Active Power (W) 4400 5500 6600 8800
Max. AC Apparent Power (VA)
*1
4400 5500 6600 8800
Nominal Power at 40℃(W) 4000 5000 6000 8000
Max Power at 40℃ (including AC
overload)(W)
4000 5000 6000 8000
Nominal Output Voltage (V) 400, 3L/N/PE
Output Voltage Range (V) 180~270 180~270 180~270 180~270
Nominal AC Grid Frequency (Hz) 50 / 60 50 / 60 50 / 60 50/60
AC Grid Frequency Range (Hz) 45~55 / 55-65
Max. Output Current (A) 6.4 8 9.6 12.8
Nominal Output Current (A) 5.8 7.2 8.7 11.6
Max. Output Fault Current (peak
and duration) (A/ms)
22/5 22/5 22/5 38/5
Inrush Current (peak and
duration) (A/us)
10/50 10/50 10/50 30/50