GREE DC INVERTER HEAT PUMP CONDENSING UNIT
58
Refrigerant charging when unit is turned on:
Step 1: Close the valve of refrigerant tank. First remove the pressure gauge lines and connect the outdoor
unit to the indoor unit. Then reconnect the pressure gauge lines. Connect the low pressure gauge line to the other
joint of gas valve and connect the high pressure gauge line to the liquid valve. Connect the middle gauge line to
the vacuum pump. Power on the vacuum pump and perform vacuum drying.
Step 2: After vacuum drying, close the high and low pressure gauge valves. Then remove the middle gauge
line from the connector of vacuum pump. Then connect to the refrigerant tank.
Step 3: Loosen the middle gauge line from the connector of pressure gauge to a proper extent and slightly
open the valve of refrigerant tank. Evacuate the middle gauge line. Then tighten up the connector again and
completely open the valve of refrigerant tank at the same time.
Step 4: Turn on the air conditioner and let it run for a while.
Step 5: Open the low pressure gauge valve (Keep the high pressure gauge valve closed). Then charge in the
remaining charging quantity m`.
Step 6: After all required refrigerant is charged in, close the valve of refrigerant tank.
Step 7: Remove the pressure gauge to finish the refrigerant charging work.
Procedure of refrigerant charging
Following is the supplementary requirement for refrigerant charging on the basis of normal procedure:
1) Make sure that when charging refrigerant into the system, no other types of refrigerant will be mixed.
The pipeline for refrigerant charging should be as short as possible to reduce the amount of refrigerant
left in it.
2) The refrigerant tank should stand erect.
3) Make sure the refrigerating system is already grounded before refrigerant charging.
4) When charging is completed (or not yet completed), stick a label on the system.
5) Before re-charging refrigerant into the system, use oxygen-free nitrogen to perform pressure test. When
charging is completed, perform leak test before trial running. Before leaving the workplace, perform a
leak test again.

Other manuals for Gree FLEXX36HP230V1AO

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree FLEXX36HP230V1AO and is the answer not in the manual?

Gree FLEXX36HP230V1AO Specifications

General IconGeneral
BrandGree
ModelFLEXX36HP230V1AO
CategoryHeat Pump
LanguageEnglish

Related product manuals