DC Inverter Multi VRF System User Manual
5
Please keep the unit away from
inflammable, explosive and
corrosive gas or waste gas.
Make sure the location has space
for heat exchange and
maintenance so that unit can
operate reliably with good
ventilation.
ODU and IDU should stay as
close as possible to shorten the
length of refrigerant pipe and
reduce bend angles.
Select a location which is out of
children’s reach. Keep the unit
away from children.
If the ODU is totally surrounded by walls, please refer to the following figures for space
dimension:
Fig.2
3.3 Piping Work Requirements
Refer to the table below for piping work requirements:
R410A Refrigerant System
Outer diameter (mm/inch)
Wall thickness(mm)
Φ6.35(1/4)
≥0.8
Φ9.52(3/8)
≥0.8
Φ12.70(1/2)
≥0.8
Φ15.9(5/8)
≥1.0
Φ19.05(3/4)
≥1.0