GMV DC Inverter VRF
60
4.4 Parameter Judgment Reference Value for Unit Normal Operation
Debugging Parameter Reference Value for DC Inverter VRF Unit
1
System
parameter
Outdoor
unit’s
parameter
Outdoor ambient
℃
— —
2
Discharge pipe
temperature of inverter
℃
● When the compressor starts running, the
normal discharge pipe of cooling or shell
top temperature is 70~95
℃
, above 10
℃
higher than the saturation temperature of
system high pressure; the normal heating
temperature is 65~90
℃
, above 10
℃
than the saturation temperature of system
—
3
Shell top tube
temperature of inverter
℃
—
4
Discharge pipe
temperature of inverter
℃
—
5
Shell top tube
temperature of inverter
℃
—
6
Temperature of
defrosting temperature
sensor
℃
● When the system is running in cooling
mode, the temperature of defrosting
temperature sensor is 5~11
℃
lower than
system high pressure;
● When the system is running in heating
mode, the temperature difference between
the defrosting temperature sensor and the
system low pressure is about 2
℃
—
7 System high pressure
℃
● The normal high pressure value of the
system is 20
℃
~55
℃
. According to the
change of ambient temperature and the
change of operating capacity of the
system, the high pressure value of the
system is 10
℃
~40
℃
higher than the
ambient temperature. The higher the
ambient temperature, the smaller the
temperature difference;
● When the unit operating in the cooling
mode at the ambient temperature of
25~35
℃
, the system high pressure value is
44~56
℃
;
● When the unit operating in the heating
mode at the ambient temperature of -
5~10
℃
, the system high pressure value is
℃
—
8 System low pressure
℃
● When the unit operating in the cooling
mode at the ambient temperature of
25~35
℃
, the system low pressure value is
0~8
℃
;
● When the unit operating in the heating
mode at the ambient temperature of -
5~10
℃
, the system low pressure value is -
℃
—
9
Opening of electronic
expansion valve of
heating
PLS
● During cooling operation, the electronic
expansion valve of heating is 3000PLS;
● During heating operation, the adjustable
range of the opening of electric expansion
valve opening is 720~3000PLS.
—