GMV DC Inverter VRF
7
ODU model
Max number of connectable
ODU model
Max number of connectable
GMV-895WM/G-X 53 GMV-2190WM/G-X 80
GMV-950WM/G-X 56 GMV-2245WM/G-X 80
GMV-1015WM/G-X 59 GMV-2295WM/G-X 80
GMV-1119W M/G-X 64 GMV-2414WM/G-X 80
GMV-1175WM/G-X 64 GMV-2470WM/G-X 80
GMV-1230WM/G-X 64 GMV-2525WM/G-X 80(85)*
GMV-1295WM/G-X 64 GMV-2590WM/G-X 80(90)*
GMV-1399WM/G-X 66 GMV-2720WM/G-X 80(100)*
GMV-1455WM/G-X 69 — —
Note:
*The maximum connection quantity of indoor unit in the brace should be engineering customized.
(2) The total capacity of indoor units should be within 50%~135% of that of outdoor units.
(3) When any one of the indoor units receives the operation command, the outdoor unit starts
running according to the required capability; when all indoor unit stops running, the outdoor unit
stops operation.
2.3 Names of Main Parts
Fig.2.3.1
2.4 The Range of Production Working Temperature
-15
℃
* ~52
℃
DB -30
℃
~24
℃
DB
℃
℃
℃
℃
*Note: Cooling at -15~-5
℃
is conditional. Please inquire our engineers for more information.
Generally, the lowest operating temperature for cooling is-5
℃
.
When the indoor units are all VRF fresh air processor, the unit operating range is as follows:
Ambient temperature: 16
℃
~45
℃
Ambient temperature: -7
℃
~16
℃
NOTE!
If exceeding the temperature range for working, the product may be damaged, which is not within
the warranty range.