Check after installation
Test operation
Test and operation
1.
Check according to the following requirement
after finishing installation.
Preparation of test operation
The client approves the air conditioner.
Specify the important notes for air conditioner to
the client.
Items to be checked Possible malfunction
The unit may drop, shake or
emit noise.
Has the unit been
installed firmly?
Is water drained well?
It may cause condensation
and water dripping.
Have you done the refri-
gerant leakage test?
It may cause insufficient
cooling(heating) capacity.
It may cause malfunction or
damaging the parts.
Is electric wiring and pip-
eline installed correctly?
It may cause malfunction or
damaging the parts.
Is the unit grounded
securely?
Does the power cord fol-
low the specification?
It may cause malfunction or
damaging the parts.
Is there any obstruction in
the air inlet and outlet?
Is heat insulation of pipe-
line sufficient?
It may cause malfunction or
damaging the parts.
The gas valve and liquid
valve of connection pipe
are open completely?
The dust and sundries
caused during installation
are removed?
It may cause condensation
and water dripping.
It may cause electric leakage.
Is the inlet and outlet of
piping hole been covered?
2.
Is the voltage of power
supply according to the
voltage marked on the
nameplate?
It may cause insufficient
cooling(heating) capacity.
6. Tighten the screw caps of valves and refriger-
ant charging vent.
Leakage detection
Use vacuum pump
Remove the valve caps on the liquid valve and
It may cause insufficient
cooling (heating) capacity.
1.
1.
2.
5. Remove the piezometer, open the valve core
Reinstall the handle.
It may cause insufficient
cooling (heating) capacity
or waster eletricity.
7.
of liquid valve and gas valve completely with
inner hexagon spanner.
piezometer
valve cap
Lo Hi
liquid valve
gas valve
refrigerant charging
vent
nut of refrigerant
charging vent
close
open
vacuum pump
inner hexagon
spanner
for 10-15min to check if the pressure of piezo-
meter remains in -0.1MPa.
4. Close the vacuum pump and maintain this sta-
tus for 1-2min to check if the pressure of piezo-
meter remains in -0.1MPa. If the pressure de-
creases, there may be leakage.
10
3.
Open the piezometer completely and operate
refrigerant charging vent of gas valve and then
connect the other charging hose to the vacuum
pump.
Method of test operation
no nottub FFO/NO sserp ,rewop eht hguorht tuP
the remote controller to start operation.
Press MODE button to select AUTO, COOL, DRY ,
si noitarepo eht rehtehw kcehc ot TAEH dna NAF
normal or not.
I
f the ambient temperature is lower than 16℃, eht
air conditioner can’t start cooling.
With leakage detector:
Check if there is leakage with leakage detector.
With soap water:
If leakage detector is not available, please use
soap water for leakage detection. Apply soap
water at the suspected position and keep the
soap water for more than 3min. If there are air
bubbles coming out of this position, there's a
leakage.
gas valve and the nut of refrigerant charging vent.
2.
Connect the charging hose of piezometer to the

Other manuals for Gree GWH18ACE-S6DBA1A/O

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GWH18ACE-S6DBA1A/O and is the answer not in the manual?

Gree GWH18ACE-S6DBA1A/O Specifications

General IconGeneral
BrandGree
ModelGWH18ACE-S6DBA1A/O
CategoryAir Conditioner
LanguageEnglish

Related product manuals