14
7.2.4
7.2.5
℃.
7.3
7.3.1
FAN mode
Indoor fan motor runs at setting fan speed:
AUTO LOW
MED HIGH
Temp. setting range is 16℃~ 30 ℃.
Auto mode
When Tamb>2 ℃, it runs at cool mode, indoor setting temp. is25
Protection Functions
Indoor antifreezing protection
When 20℃≤Tamb≤2 6℃ , it will run in dry mode, the inner setting temp. is 24℃ .
When Tamb<2 0℃, it will run in HEAT mode, inner setting temp. is 20℃, Tamb≥ 24℃, quit HEAT mode.
If it is cooling only type unit, when Tamb<2 0℃, it will run in FAN mode, inner setting temp. is 24℃.
When each mode start up, at least running for 30 seconds, Tamb then switch to AUTO mode running status.
Teva<- 2℃, it shows E2, compressor stops running, outdoor and indoor fan motor,
swing motor keep original running; when Teva>6℃, com pressor has stopped 4min,
When in COOL mode, compressor started up 10min, when continuously 3min detected