Specifications
Table 1 Line Mode Specifications
INVERTER MODEL
SPF 3000T HVM-G2
Input Voltage Waveform
Pure sine wave/ same as input (bypass mode)
Nominal Input Voltage
230Vac
Input voltage range
184~272Vac
UPS
);
154~272Vac
APL
Low Loss Voltage
184Vac±7V(UPS); 154Vac±7V(APL)
Low Loss Return Voltage
194Vac±7V(UPS); 164Vac±7V(APL)
High Loss Voltage
>272Vac±7V
High Loss Return Voltage
<262Vac±7V
Nominal Input Frequency
50Hz / 60Hz (Auto detection)
Input Frequency range
45-65Hz
Low Loss Frequency
45±1Hz
Low Loss Return Frequency
47±1Hz
High Loss Frequency
65
±
1Hz
High Loss Return Frequency
63±1Hz
Efficiency (Line Mode)
>95% ( Rated R load, battery full charged )
Input Current
Max 30A
Transfer Time
Typical 10ms