EasyManuals Logo
Home>Grundfos>Engine>MGE 112

Grundfos MGE 112 User Manual

Grundfos MGE 112
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
English (GB)
23
2. If the light diode is flashing, the functional module is working
correctly. The fault may then be in the control panel. See
section 7.4 Replacing the control panel.
If the status diode of the functional module is off, check if the
power module supplies voltage by measuring 8.5 VDC on the
VFE plug connection between the functional module and the
power module (see fig. 54, J15). If no voltage is measured, the
connection between the modules or the power module is
defective.
If the VFE voltage to the functional module is okay, check if the
voltage between the reference point and the other measuring
points is okay. The voltage values apply to an operating motor.
Fig. 54 Measuring voltage on the functional module
To measure the voltage listed in the table below, you must use the
same reference point (ref.) seen on the figure above.
Measure the DC voltage from e.g. "ref." to "1". The measure
should be between 14.5 V and 15.7 V.
Replace the functional module if the voltage is not correct. See
section 7.7 Replacing the functional module.
TM06 7718 3816
1
ref.
2
3
4
5
6
6
5
J15
VFE
Use a correctly calibrated measuring instrument.
Pos.
Control voltage [VDC]
Minimum Nominal Maximum
VFE
(J15)
8.5
1 14.5 15.1 15.7
2 4.8 5 5.2
3 4.8 5 5.2
4 3.2 3.3 3.4
5 23 23.9 24.8
6 4.8 5 5.2
ref. GND

Other manuals for Grundfos MGE 112

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos MGE 112 and is the answer not in the manual?

Grundfos MGE 112 Specifications

General IconGeneral
BrandGrundfos
ModelMGE 112
CategoryEngine
LanguageEnglish

Related product manuals