14. Fault finding the product
Noise in the pump
Cause
There is air in the pump.
Remedy
Let the pump run. The pump vents itself over time.
Cause
Inlet pressure is too low.
Remedy
Increase the system pressure or check the air volume in the expansion tank, if installed.
Noise in the system
Cause
There is air in the system.
Remedy
Vent the system.
Cause
Differential pressure is too high.
Remedy
Reduce the pump performance at the pump or external controller.
Pump is not running, no power supply
Cause
System is switched off.
Remedy
Check the system controller.
Cause
A fuse in the installation is blown.
Remedy
Replace the fuse.
Cause
Power supply failure.
Remedy
Check the power supply.
Pump is not running, normal power supply
Cause
Controller is switched off.
Remedy
Check the controller and its settings.
Cause
Pump is blocked by impurities.