COMPACT CASSETTE TECHNICAL OVERVIEW
D-5
ENGLISH
Testing
Accessing the Blower Motor and Condensate Pump
1. Disconnect power to the outdoor unit.
2. Remove the louver assembly.
Removing Fan Motor
1. Remove holding nut from fan blade.
Removing Condensate Pump
1. Remove screws holding condensate pump and oat switch
in position.
2. Disconnect condensate hose from condensate pump.
3. Remove assembly.
8. Slide condensate pan from cassette.
2. Fan blade will slide o motor shaft.
3. Remove Phillips head screw holding cover plate over motor
wiring leads.
4. Remove 3 nuts that hold fan motor in place.
5. Fan motor will come loose.
3. Disconnect the main power wire to the indoor unit.
4. Unplug the condensate pump and oat switch from wiring
harness.
5. Unplug fan motor from wiring harness.
6. Remove ground wire from ground screw on electrical
box. Remove electrical box.
7. Remove 5 screws holding foam condensate pan bottom in
place.