4
3. Combination method
Capacity Combination model
3≤x≤7KW AH1-070B
7<x≤14KW AH1-140B
14<x≤28KW AH1-280B
28<x≤56KW AH1-560B
56<x≤73KW AH1-730B
73<x≤112KW AH1-560B+AH1-560B
112<x≤146KW AH1-730B+AH1-730B
146<x≤168KW AH1-560B+AH1-560B+AH1-560B
168<x≤219KW AH1-730B+AH1-730B+AH1-730B
219<x≤224KW AH1-560B+AH1-560B+AH1-560B+AH1-560B
224<x≤292KW AH1-730B+AH1-730B+AH1-730B+AH1-730B
Note:
The above is the combination method for single heat exchanger, when multiple heat exchangers need to be
matched according to the capacity of each heat exchanger
Length
Pipe length between outdoot unit& AHU VALVE Min5m
max.50m
Pipe length between AHU valve & AHU Max.5m
Drop between outdoor unit & AHU valve ±30m
Drop between AHU & AHU valve ±5m
Note:
• Non-mixing connection: AHU connection rate 90 ~ 110%
• When mixing:
1. The total indoor unit connection rate is 50 ~ 110%, of which the air conditioner
internal unit is not less than 50%
2. A system can only be connected to an AHU and an AHU valve box