EasyManuals Logo

Haier MRVII-S AU48NFIERA User Manual

Haier MRVII-S AU48NFIERA
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
38
(3) Cooling operation conrmation
Start
Set the mode as COOL: press the button
for over 5 seconds at OFF state
No
No
No
No
No
No
No
Once outdoor stops, re-start up
the unit 2 and a half minutes
later
If blowing out cold air
If the ventilation is good
Conrm the running state of the
compressor, indoor EEV
If the louver direction
Make all indoors running
simultaneously
Temp. difference between air
outlet and air inlet is good
If running voltage is
proper (380V±10%)
If running current is in the
range of rated current±15%
(at the max. frequency)
If running pressure is proper
Normal
Yes
Yes
Yes
Yes
Yes
Yes
Check the power source
voltage, the power cable spec
and the power cable terminal
installation
Check indoor/outdoor temp.,
pipe length, refrigerant
charging amount, indoor
capacity, compressor
running frequency, outdoor
fan operation, and if
compressor sounds
abnormal noise
Check every indoor

Other manuals for Haier MRVII-S AU48NFIERA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier MRVII-S AU48NFIERA and is the answer not in the manual?

Haier MRVII-S AU48NFIERA Specifications

General IconGeneral
BrandHaier
ModelMRVII-S AU48NFIERA
CategoryAir Conditioner
LanguageEnglish

Related product manuals