Copyright © 2020 Haskris REV102920
1
www.haskris.com
776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph: +1-847-956-6420 | fx: +1-847-956-6595 | email: service@haskris.com
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 1: Temperature Control
• Your Haskris will have one of three different types of controller. Use table 1-1 to identify the relevant controller.
• The controller may appear different than examples. Contact Haskris if you are not sure what type you have.
• Adjust supply temperature while under heat load.
• Allow 15-30 minutes for the supply temperature to stabilize after an adjustment.
• Consult a dew point chart to select a supply uid temperature that will minimize condensation.
• If no heat load is applied, the unit may “over-cool”.
Electronic Temperature Controllers
ON/OFF
Cycling Control
Section 1.1
Parametric
Control
Section 1.2
Programmable
Logic Control
Section 1.3
Table 1-1