SJ100 Series Supplemental Sheet (NBM585XA-12)
ATTENTION
Note 1:
The revision level of the MFG No. distinguishes the following changes in Function Codes A81, C31
and C32
. The Inverter MGF No. is shown on the Specification Label (Nameplate), located on the right
side of the housing. The changes apply to inverters, which carry a revision code per the table below.
When you copy parameters between units manufactured before and after this change with a copy unit,
confirm Function Codes C31 and C32.
Example of MFG No. :
112H
T123451J001
Revision
A…K…1A…1K…2A…2H…
Revision Increment--------
Æ
Page
Changes
3-18
Inverter Models
Revision
before change
Applied
Revision
SJ100-002NFU 2E 2H
SJ100-004-022NFU 2G 2H
SJ100-037LFU 2E 2H
SJ100-055,075LFU K M
SJ100-004HFU 2F 2H
SJ100-007-040HFU 2G 2H
SJ100-055,075HFU L M
OLD DEFAULT SETTING:
“A” Function
Run-
Defaults DOP,DRW,DOP+
Func.
Code
Name Description
time
Edit
EU/
US
Units
Func.
Code
Name
A81 AVR function
select
Automatic (output) voltage
regulation, selects from three
types of AVR functions, three
option codes:
00…AVR enabled
01…AVR disabled
02…AVR enabled except
during deceleration
02
- F-03 AVR
MODE
NEW DEFAULT SETTING:
*Inverters manufactured after the revision as defined in Note 1 will have the following settings:
“A” Function
Run-
Defaults DOP,DRW,DOP+
Func.
Code
Name Description
time
Edit
EU/
US
Units
Func.
Code
Name
A81 AVR function
select
Automatic (output) voltage
regulation, selects from three
types of AVR functions, three
option codes:
00…AVR enabled
01…AVR disabled
02…AVR enabled except
during deceleration
00
- F-03 AVR
MODE