EasyManuals Logo
Home>Honeywell>Controller>DBC2000E10 Series

Honeywell DBC2000E10 Series User Manual

Honeywell DBC2000E10 Series
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
ENS7003R16 KO65 2013
26
Table a.
Volumes in dm3 for gas valves like Honeywell VE-series (Vp) with pipe length L (including V1 and V2). For combi blocks, like
VQ-M series and direct linked valves, use the values shown under L=0m.
Diameter
Length between valves [m]
0
0.5
1
1.5
2
per extra
meter
¼”
0.06
0.1
0.14
0.18
0.22
0.08
½”
0.06
0.15
0.24
0.33
0.42
0.18
¾”
0.12
0.28
0.43
0.59
0.74
0.31
1”
0.19
0.44
0.68
0.93
1.2
0.49
1¼”
0.69
1.1
1.5
1.9
2.3
0.8
1½”
0.71
1.4
2.0
2.7
3.3
1.3
2”
1.3
2.3
3.3
4.2
5.2
2.0
2½”
2.7
4.4
6.0
7.7
9.3
3.3
3”
2.9
5.4
7.9
10
13
5
DN65
3.2
4.9
7.5
8.2
9.8
3.3
DN80
4.4
6.9
9.4
12
14
5.0
DN100
6.5
10.5
14.4
18
22
7.9
Threaded connections: sizes in inches.
Flanged connections: sizes in DN
If L = 0m it means that valves are directly linked without pipe connections. Also applicable for combi-blocks (VQ-M series).

Table of Contents

Other manuals for Honeywell DBC2000E10 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell DBC2000E10 Series and is the answer not in the manual?

Honeywell DBC2000E10 Series Specifications

General IconGeneral
BrandHoneywell
ModelDBC2000E10 Series
CategoryController
LanguageEnglish

Related product manuals