EasyManuals Logo
Home>Honeywell>I/O Systems>Excel 5000 open XFL523B

Honeywell Excel 5000 open XFL523B User Manual

Honeywell Excel 5000 open XFL523B
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
® U.S. Registered Trademark
Copyright © 2002 Honeywell Inc. • All Rights Reserved EN0B-0090GE51 R0802
74-2145-2
Distributed I/O
XFL521B, 522B,
523B, AND 524B MODULES
PRODUCT DATA
FEATURES
LONMARK™ compliant
2-wire LONWORKS
®
bus interface between controller
and I/O
No additional field terminals required
Usable with Excel 500 controllers in conjunction with
standard internal I/O modules
Automatic binding and commissioning to Excel 500
controllers when using CARE
Connector module with sliding bus connector
(eliminating the need to wire together neighboring
modules)
Fast connection due to spring clamp terminals
Module exchange during operation
Alarm in case of defective module
Mechanical coding prevents mismatching of modules
Power LED (L1, green) and L
ONWORKS service LED
(L2, red) on all electronics modules
Status LEDs for outputs and digital inputs
Optional manual override modules for analog and
digital output modules with feedback
XILON for wiring test
GENERAL
The XFL521B, 522B, 523B, and 524B modules are LONMARK
compliant digital and analog I/O modules which can be
installed at strategic locations within a building. These
modules convert sensor readings and provide output signals
used for operating actuators via L
ONWORKS standard network
variables (SNVTs). Each Distributed I/O module plugs into a
base terminal block allowing communication with controllers
via the built-in Echelon
®
LONWORKS bus interface. The ter-
minal block provides spring clamp terminals for easy connec-
tion of field cables from the various sensors and actuators.
The modular system allows Distributed I/O modules to be
removed from the system without disturbing other modules.
The module with terminal block mounts easily onto a DIN rail.
When using CARE, the Distributed I/O modules can be
automatically bound and commissioned to the Excel 500
CPU (XC5010C, XC5210C, XCL5010) and XL50. When the
modules are used by other controllers, provided plug-ins
permit the modules to be commissioned by CARE 4.0 or by
any LNS network management tool.
DESCRIPTION
These Distributed I/O modules use a Neuron® chip and an
FTT-10A free topology transceiver for communication on a
L
ONWORKS bus and comply with LONMARK Application Layer
Guidelines V3.2.
Table 1. Modules and accessories
Item Description
XFL521B Analog input module
XFL522B Analog output module
XFL523B Digital input module
XFL524B Digital output module
XSL511 LONWORKS connector module
XSL512 Manual terminal disconnect module
XSL513 Terminal block for XFL521x, 522x, 523x
XSL514 Terminal block for XFL524x
XFR522A Analog output manual override module
XFR524A Digital output manual override module
XAL-Code To prevent mismatching modules
XAL-Term Interface to the LONWORKS bus
209541B LonWorks bus termination modules
XAL 2 Cover release tool
XAL 1 Swivel label (for manual override modules)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Excel 5000 open XFL523B and is the answer not in the manual?

Honeywell Excel 5000 open XFL523B Specifications

General IconGeneral
BrandHoneywell
ModelExcel 5000 open XFL523B
CategoryI/O Systems
LanguageEnglish

Related product manuals