DISTRIBUTED I/O – PRODUCT DATA
EN0B-0090GE51 R0316 4
TRANSFORMER
MAX. 550 ft (170 m)
MIN. 14 AWG
(
2.5 mm
)
2
PRIMARY
VOLTAGE
Y
GND
24 Vac
2
24 V
24 V
~
1
0000056a
Fig. 2. Cabling of actuator with 24 Vac supply and max.
550 ft (170 m).
IMPORTANT
It is recommend to install a fuse on the secondary side
of the transformer in order to protect the devices from
miswiring.
If the distance between the controller and actuator or sensor
with 24 Vac supply is greater than 550 ft (170 m), a separate
external transformer for the actuator or sensor is necessary.
Fig.3. Cabling of actuator with 24 Vac supply from
external transformer and max. 1300 ft (400 m).