DOC-02-159:rev C - Page 1 of 8
AFP-3030
Intelligent Fire Alarm Control Panel
Intelligent Fire Systems
GENERAL
The AFP-3030 is an intelligent Fire Alarm Control Panel (FACP)
with a flexible and scaleable architecture which makes it suitable
for virtually any application including large scale networked
facilities. Fire emergency detection and evacuation are extremely
critical to life safety, and the AFP-3030 is ideally suited for these
applications.
The AFP-3030 is part of the ONYX® Series of products from
NOTIFIER. With one to ten Signaling Line Circuits (SLCs), the
AFP-3030 supports up to 3,180 intelligent addressable devices
per panel and is networkable up to 200 nodes.
A host of other options are available, including single-
or multichannel voice; LED, LCD, or PC-based graphic
annunciators; networking; advanced detection products for
challenging environments, and many additional options.
Connectivity with a range of NOTI•FIRE•NET™ integration
options such as Bacnet, Modbus, OnyxWorks and
Notifier WebServer (NWS-3) permit the AFP-3030 and
NOTI•FIRE•NET™ to integrate into critical component building
management systems.
FEATURES
One to ten isolated intelligent Signaling Line Circuits
Up to 159 detectors and 159 modules per SLC, 318
devices per loop / 3,180 per FACP (or network node)
Detectors can be any mix of ionization, photo, laser
photo, thermal, or multi-criteria detectors; modules
can be addressable manual call points, normally open
contact devices, two-wire smoke detectors, notification,
relay or 4-20 mA modules
Large 640-character LCD backlit displayor display-less
(a node on a network)
Network up to 200 nodes with high-speed Noti-Fire-Net
VeriFire Tools non-proprietary online/offline program, test
and reporting PC software.
Weekly Occupancy Schedules allow changing sensitivity
by time of day and day of week
With built-in SLC Local mode operation; the system is
capable of activating sounders and relays if a fire alarm
condition is present even if the central processing unit
(CPU) fails
Range of annunciators for ancillary display & control
History file with 4000-event capacity plus separate
1000-event alarm-only file
Advanced history filters allow sorting by event, time,
date, or address
Alarm Verification Facility (AVF) selection per point, with
automatic counter
Auto-programming and Walk Test reports
Alarm delay operation
Field-programmable on panel with QWERTY keypad
Non-alarm points for lower priority functions
Remote Silence, System Reset, Evacuate via monitor
modules
Support for AS1668.1 compliant smoke control with
SCS Series smoke control system
AFP-3030 in CAB-900 and CAB650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier AFP-3030 and is the answer not in the manual?

Honeywell Notifier AFP-3030 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier AFP-3030
CategoryControl Panel
LanguageEnglish