X-XX UL
INSTALLATION INSTRUCTIONS
®U.S. Registered Trademark
Copyright © 2002 Honeywell • • All Rights Reserved
T8000, T8001
Programmable Thermostat
APPLICATION
The T8000, T8001 Thermostats provide single-stage,
programmable temperature control for 24 Vac heating-
cooling systems with manual changeover from heat to
cool. Heating cycle rate is selectable at 1, 3, 4, 5, 6, 9, or
12 cph. Cooling cycle rate is fixed at 3 cph. Temperature
indication can be set for °F or °C.
The T8001 Thermostat is powered directly from the
system transformer. The T8000 Thermostat is powered
through the heating/cooling system controls. Batteries are
not required because setpoints are held permanently by
non-volatile memory.
The T8000 and T8001 include a thermostat, wallplate and
owner’s guide. A 7 3/8 in. (188 mm) x 5 3/4 in. (146 mm)
decorator cover plate (for covering wall marks) is available
separately. Order Honeywell part no. 209649A (taupe) or
part no. 209649B (white).
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of it properly.
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of a control.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Hazardous Voltage.
Can damage heating/cooling system.
Disconnect power at furnace or main breaker/
fuse box.
Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1. Do not install the thermostat where it can be
affected by:
drafts or dead spots behind doors and in corners.
hot or cold air from ducts.
radiant heat from the sun or appliances.
concealed pipes and chimneys.
unheated (uncooled) areas such as an outside wall
behind the thermostat.
Mounting Wallplate to Wall
IMPORTANT
Level only for appearance. The thermostat
functions normally even when not level.
Mount wallplate and the thermostat with the screws
provided (see Fig. 2) as follows:
1. Place the wallplate at the desired location on the
wall.
2. Pull the thermostat wire through the wallplate
entrance hole.
3. Fasten the wallplate to the wall using the anchors
and screws provided.
4. After wiring the wallplate, plug the hole with non-
flammable insulation to prevent drafts from affecting
the thermostat; see Wiring section.
Table 1. Description of Thermostats.
Model System Changeover System Selection Fan Selection Powering Method
T8001 Heat-Cool Manual Cool-Off-Heat Auto-On Hardwired
T8000 Heat-Cool Manual Cool-Off-Heat Auto-On Power Stealing
69-1432-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell T8001 and is the answer not in the manual?

Honeywell T8001 Specifications

General IconGeneral
BrandHoneywell
ModelT8001
CategoryThermostat
LanguageEnglish

Related product manuals