5.3 Battery module replacement
Safety recommendations
Warning: To prevent personal injury from hazardous energy:
This operation must be performed when the UPS is switched o and unplugged from the AC source.
Do not disconnect the connector while the unit is operating from the AC mains or in reserve mode.
The battery connection must not be disconnected while running in reserve mode.
The battery can cause electrocution and high short-circuit currents. The following safety precautions
are required before servicing the battery components:
Remove watches, rings, bracelets, and all other metal objects from the hands and arms.
Use tools with an insulated handle.
Do not place tools or metal parts on top of batteries.
Replacing the batteries
Read and observe the requirements in "Important battery safety information" and "Battery care and
storage guidelines" in this section before battery module replacement.
Follow the instructions in this section to replace the battery module.
Note: Replace all battery modules at the same time.
Important battery safety information
Warning: The unit contains sealed lead-acid battery modules. To prevent re or chemical burns:
Do not attempt to recharge batteries after removal from the unit.
Do not disassemble, crush, or puncture the batteries.
Do not short the external contacts of the batteries.
Do not immerse the batteries in water.
Do not expose to temperatures higher than 60°C (140°F).
Battery care and storage guidelines
Caution: Because of the short shelf life of the batteries, avoid storing a battery spare as a
backup. Do not maintain an inventory of spare batteries on site unless a procedure to keep
these batteries charged while in storage is implemented.
To maintain the batteries:
Minimize the amount of time the UPS uses battery power by matching the UPS conguration with the utility vol-
tage (see "6.1 HP R/T2200 G4 NA/JP UPS and HP R/T3000 G4 LV NA/JP UPS" on page 29 and "6.2 HP R/T3000 G4
HV NA/JP UPS and HP R/T3000 G4 INTL UPS" on page 30).
Keep the area around the UPS clean and dust-free. If the environment is very dusty, clean the outside of the UPS
regularly with a vacuum cleaner.
Battery module removal
A
B
5. Maintenance
A
Remove the middle
panel.
B
Remove the left-hand
side of the bezel by
pushing the button and
sliding the part to the
left.