This water heater is certied for indoor use only. DO NOT INSTALL
OUTDOORS. Outdoor installations ARE NOT covered by warranty.
Choose a location for the water heater as centralized to the piping
system as possible. Also, locate the water heater and domestic water
piping where it will not be exposed to freezing temperatures. All
piping should be insulated. Additionally, place the water heater so that
the drain, controls, and inlets/outlets are easily accessible.
NOTE: To save on heating costs and improve energy eciency keep
the distance between the boiler and water heater to a minimum
to reduce heat loss from excess piping and keep friction loss at a
minimum. Ensure all piping between the boiler and water heater is
properly insulated to minimize heat loss.
The water heater may be located some distance from the boiler
provided the circulator meets ow requirements through the coil. The
greater the distance from the water heater to the boiler the longer the
response will be to a call for hot water.
This water heater must be installed vertical on a level surface.
NOTE: In the State of California, the water heater must be braced,
anchored, or strapped to avoid moving during an earthquake. Contact
local utilities for code requirements in your area. Visit http://www.dsa.
dgs.ca.gov or call 1-916-445-8100 and request instructions.
However, applicable codes shall govern installation. For residential
water heaters of a capacity greater than 52 gallons, consult the local
building jurisdiction for acceptable bracing procedures.
NOTE: If you do not provide the minimum clearances shown in
Figure 1, it might not be possible to service the water heater without
removing it from the space.
NOTE: A combustible door or removable panel is acceptable front
clearance.
LEAST
LP-200-K
4/21/11
RECOMMENDED SERVICE CLEARANCE
Figure 1 - Drain Pan Installation and Recommended Service Clearances
Ensure the location can support the entire lled weight of the water
heater. Failure to properly support the water heater could result in
property damage, severe personal injury, or death.
This water heater must not be located near ammable liquids such
as gasoline, butane, liqueed propane, adhesives, solvents, paint
thinners, etc., as the controls of this water heater could ignite these
vapors and cause an explosion resulting in property damage, severe
personal injury, or death.
B. Performance and Sizing Guidelines
NOTE: The table below describes the minimum BTU/H required to
achieve the listed rst hour rating. The mass of the boiler will aect
recovery time. More boiler mass equals longer recovery time.
MODEL
GROSS BOILER
OUTPUT
140
o
F
90
o
F Δ T
127
o
F
77
o
F Δ T
115
o
F
65
o
F Δ T
SSC-35 53,000 112 125 152
SSC-50 86,000 190 213 258
SSC-80 91,000 198 221 270
SSC-119 108,000 268 300 364
Table 2 - Water Heater Performance and Sizing Guidelines
C. Anode Rod
This water heater is equipped with a magnesium anode rod. Anode
rods are sacricial components that counteract water chemistry to
minimize or eliminate tank corrosion.
The anode rod should be inspected annually and replaced as necessary
to prolong tank life. Have the supply water quality professionally
analyzed, as local water conditions will inuence the duration for
inspection and replacement of the anode rod.
The use of a water softener may increase the speed of anode
consumption. More frequent inspection of the anode is needed when
using softened or treated water.
Water with high sulfate and/or mineral content can produce a rotten
egg odor in heated water. Chlorinating the water supply may minimize
this problem.
NOTE: Failure of a heat exchanger due to lime scale build-up on the
heating surface, low pH, or other imbalance IS NOT covered by the
warranty.
NOTE: Do not remove the anode rod from an operating water heater.
Operating the water heater without the anode rod will shorten the life
of the tank and VOID the warranty.
This water heater must be installed upright in the vertical position as
described in this manual. DO NOT attempt to install this water heater
in any other orientation. Doing so will result in improper water heater
operation and property damage, and could result in serious personal
injury or death.
High heat sources (generating heat 100
o
F / 37
o
C or greater, such as
stove pipes, space heaters, etc.) may damage plastic components
of the water heater as well as plastic vent pipe materials. Such
damages ARE NOT covered by warranty. It is recommended to keep
a minimum clearance of 8” from high heat sources. Observe heat
source manufacturer instructions, as well as local, state, provincial,
and national codes, laws, regulations, and ordinances when installing
this water heater and related components near high heat sources.