3 Installing the UPS
Copyright © Huawei Technologies Co., Ltd.
30
Figure 3-21 Connecting cables to the 3KRTL UPS input
3.5 Installation Verification
Table 3-2 gives the installation verification checklist.
Table 3-2 Installation verification checklist
No.
Item
Acceptance Criterion
1
Cable routing
Cable routing meets engineering requirements.
2
Cable connections
Power cables and battery cables are tightened to
specified torques using a torque wrench, connected
correctly, and free of damage.
3
Cable connections for
USB ports and network
ports
Cables to USB ports and network ports are connected
correctly and securely.
4
Cable labels
Labels are neatly attached to both ends of each cable,
and the information on the labels is concise and
understandable.
5
Ground cable
connection
The ground cable is securely connected to the
equipment room ground bar. Measure the resistance
between the UPS ground cable and the equipment room
ground bar, which must be less than 0.1 ohm.
6
Distances between cable
ties
Distances between cable ties are the same, and no burr
exists.
7
Operating environment
Clean the conductive air and other sundries.

Other manuals for Huawei UPS2000-G-3KRTS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-3KRTS and is the answer not in the manual?

Huawei UPS2000-G-3KRTS Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-3KRTS
CategoryUPS
LanguageEnglish

Related product manuals