1
VFC 15-150 / VFC 45-225
NATURAL GAS coNveRSioN PARTS KiT# P-176
120-170 R2
DANGER
Check the rating plate of the boiler
to ensure it is congured for the
fuel you are using.
Failure to perform the proper fuel
conversion when required can
result in an immediate hazard.
Operating any IBC boiler using a
fuel other than the fuel listed on
its rating plate is prohibited. If
these instructions are not followed
exactly, a dangerous situation can
result, leading to re, explosion or
production of carbon monoxide,
which may cause property damage,
personal injury, or loss of life.
NOTE
These instructions are to be closely followed, and referenced to the details in
the boiler’s current certied Installation and Operating Instruction Manual.
Important Note: If converting from Propane to Natural Gas - Order Propane
to Natural Gas Conversion Kit, IBC Part# P-174 from your authorized IBC
Distributor.
MODEL NUMBER NATURAL GAS
TO PROPANE
PROPANE TO
NATURAL GAS
Table 1: Fuel Conversion Kits
•
•
•
•
WARNING
This conversion kit shall be installed by a qualied service agency in accordance with the manufacturer’s
instructions and all applicable codes and requirements of the authority having jurisdiction. If the information
in these instructions is not followed exactly, a re, an explosion or production of carbon monoxide may result
causing property damage, personal injury or loss of life. The qualied service agency is responsible for the
proper installation of this kit. The installation is not proper and complete until the operation of the converted
appliance is checked as specied in the manufacturer’s instructions supplied with the kit.