IBM 3000VA LCD 3U Rack Uninterruptible Power Supply for IBM System x 5
Specifications
Table 3 lists the specifications for the three 3000VA UPS models.
Table 3. Specifications (Part 1 of 2)
Specification IBM 3000VA LCD 3U
Rack UPS (100V/120V)
IBM 3000VA LCD 3U
Rack UPS (200V/208V)
IBM 3000VA LCD 3U
Rack UPS (230V)
IBM part number 5395-3AX 5395-3JX 5395-3KX
VA/Watts rating 2880 VA / 2700W (120V)
2300 VA / 2300W (100V)
3000 VA / 2700W 3000 VA / 2700W
Nominal output voltage
(Vac)
100/120V AC 208V AC 230V AC
Load groups Two Two Two
Output connections One NEMA L5-20R
Two NEMA 5-20R
Two IEC 320 C19
Two IEC 320 C13
Two NEMA L6-20R
Two IEC 320 C19
Two IEC 320 C13
Two IEC 320 C19
Eight IEC 320 C13
Nominal output voltage
regulation
92-108V (100V)
106-132V (120V)
184-228V (208V) 208-253V (230V)
Input
Nominal input voltage
(auto sensing at first
power-up)
100/120V 208V 230V
Input amperage 30A 20A 16A
Input frequency (auto
sensing)
50/60 Hz +/- 3 Hz 50/60 Hz +/- 3 Hz 50/60 Hz +/- 3 Hz
Input connection Type NEMA L5-30P (fixed line
cord)
IEC 320-C20 IEC 320-C20
Included line (input) cords NEMA L5-30P 2.0 m
(fixed)
(1) IEC 320 C19 to NEMA
L6-20P 4.3 m
(2) IEC 320 C19 to LP-3
4.3 m (Taiwan)
Optional country specific
line cords (See Table 2)
Input voltage range, mains
operations
84-121V for 100V
97-145V for 120V
155-255V for 208V 160V-286V for 230V
Batteries
Typical backup times See Table 4 See Table 5 See Table 6
Battery type Valve Regulated Lead Acid (VRLA) – maintenance-free, sealed, leak-proof
Optional External Battery
Pack
Yes, 69Y1982 Yes, 69Y1982 Yes, 69Y1982
Typical recharge time 4 hours to 90% charge from a UPS/battery discharge of 50% rated load