a. Align the left extension panel (H) with the rack corner post.
b. Using a #2 Phillips head screwdriver, tighten the seven M5 screws with captive star washer (I) into
the rack. Use a torque screwdriver to tighten the screws to 2.5 Nm (22.1 lb).
3. Install the right extension panel.
To install the right extension panel, perform the following tasks:
a. Align the right extension panel (D) with the right side covers.
b. Using a #2 Phillips head screwdriver, tighten the seven M5 screws with captive star washer (E) into
the rack. Use a torque screwdriver to tighten the screws to 2.5 Nm (22.1 lb).
4. Install the top cap.
To install the top cap, perform the following task:
a. Align the top cap (A) with the installed extension panels.
b. Using a #2 Phillips head screwdriver, insert and tighten the M5 screws with captive star washers
(B) into each of the screw holes. Use a torque screwdriver to tighten the screws to 2.5 Nm (22.1 lb).
c. Install the nut clips (C).
5. Install the bottom cap.
To place the bottom cap, perform the following task:
a. Align the bottom cap (F) with the installed extension panels.
b. Using a #2 Phillips head screwdriver, insert and tighten the M5 screws (G) with captive star
washers into each of the screw holes. Use a torque screwdriver to tighten the screws to 2.5 Nm
(22.1 lb).
6. Install the rear hinge assemblies (top and bottom) and the latch plate that you previously removed
from the frame onto the extension panel.
Installing the airflow management kit
You might need to install an airflow management kit on your rack.
About this task
To install an airflow management kit to the rack, complete the following tasks:
Procedure
1. Install the access panel. To install the access panel, perform the following tasks:
a. Align the vertical edge of the access panel with the rack.
b. Rotate the access panel (1) until it is closed (2).
Racks and rack features
131

Other manuals for IBM 7014-T42

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM 7014-T42 and is the answer not in the manual?

IBM 7014-T42 Specifications

General IconGeneral
BrandIBM
Model7014-T42
CategoryRacks & Stands
LanguageEnglish

Related product manuals