pressure jet
Natural gas, oil fired or dual fuel
High efficiency
Minimal emissions
3 pass heat exchanger
Compact size
Meets Building Regulations 2006 (Part L2)
Model GTE5 GTE6 GTE7 GTE8 GTE9
Sections 5 6 7 8 9
Output (kW) 140 180 230 280 330
Height 1297
Width 796
Depth 1151 1311 1471 1631 1791
Flow/Return Connections (DN flange)
65
Flue Size (mm) 180 180 200 200 200
Maximum Working Pressure (bar)
6
Water Content (L) 116 136 156 176 196
Approx Dry Weight (kg) 748 906 1043 1165 1289
Front (mm) 1500
Back (mm) 1000
Side - non hinge (mm) 100
Side - door hinge (mm) 500 or 200 + burner length
General Data Harrier GTE (105 - 330)
Option Kits
Boiler
Clearances
Boiler Harrier GTE
Hours run meter(s)
De Luxe control panel (High / Low operation)
Flue gas thermometer
GT Condenser
Harrier GTE 105 - 330kW