Settings
6 720 643 409 (2010/03)
63
>> Highest permitted flow temperature T1
1)
The value that is set in Lowest permitted flow
temperature T1.
>> Lowest permitted flow temperature T1
B Set the highest and lowest permitted temperature for
T1. Ensure that the value corresponds with the
selected curve and possible curve adjustments.
B Check also that the highest temperature T1 with
Underfloor does not exceed the permitted value for
the type of floor used.
>> Heat curve
The settings are the same as for Circuit 1.
>> Room sensor
The settings are the same as for Circuit 1.
>> Room temperature program
The settings are the same as for Circuit 1, except that
Copy to all heating circuits is not included.
>> Regulator settings
The mixing valve is controlled with PID regulator in order
to reach the flow set point value when there is a need.
The signal determines how much the opening of the
mixing valve should change. It is calculated with short
time intervals.
>> Regulator settings
>>> P constant
>>> I constant
>>> D constant
>>> Minimum PID signal
>>> Maximum PID signal
>>> Mixing valve running time
The right point of the curve (-35 °C) can be
changed in Minimum outdoor
temperature(Æ Chapter 15.1). Set value
applies for all heat curves.
A change of the right point affects the flow
temperature for all outdoor temperatures
that are lower than the set temperature.
Factory setting 80.0 °C
Lowest value
1)
Highest value 100.0 °C
Tab. 70 Radiator
Factory setting 45.0 °C
Lowest value
1)
Highest value 45.0 °C
Tab. 71 Underfloor
Factory setting 10.0 °C
Lowest value 10.0 °C
Highest value 80.0 °C
Tab. 72 Radiator
Factory setting 10.0 °C
Lowest value 10.0 °C
Highest value 45.0 °C
Tab. 73 Underfloor
Factory setting 1.0
Lowest value 0.1
Highest value 30.0
Tab. 74 P constant
Factory setting 300.0
Lowest value 5.0
Highest value 600.0
Tab. 75 I constant
Factory setting 0.0
Lowest value 0.0
Highest value 10.0
Tab. 76 D constant
Factory setting 0%
Lowest value 0%
Highest value 100%
Tab. 77 Minimum PID signal
Factory setting 100%
Lowest value 0%
Highest value 100%
Tab. 78 Maximum PID signal
Factory setting 300s
Lowest value 1s
Highest value 6000s
Tab. 79 Mixing valve running time