Wiring
Proper grounding and wiring of all electrical equipment is important to help ensure the optimum
operation of the IXrouter and to provide additional electrical noise protection for your application.
Digital input
The function of the digital input is configurable via the IXplatform. Instructions can be found on
support.ixon.co/docs/digital-input. The V- from the power supply is used as common ground.
Type
Optocoupler
DI voltage range
0-29 VDC
DI OFF state voltage range
0-3 VDC
DI ON state voltage range
7-29 VDC
DI ON state current range
2-5 mA (typically)
Shield
Connect the Shield pin of the IXrouter with the protective earth conductor (PE), min. core diameter
Cu 1.5 mm².