If hot water is available, press the MODE button
repeatedly until the HEAT icon appears on the
display. Press the UP or DOWN buttons until the
set temperature is 10 degrees above room
temperature. The hot water valve will open and the
fan will be running. The strip heat will be locked
out if hot water is available.
If cold water is available, press the MODE button
repeatedly until the COOL icon appears on the
display. Press the UP or DOWN buttons until the
set temperature is 10 degrees below room
temperature. The cold water valve will open and
the fan will be running.
If hot water is not available, but your unit is
equipped with a strip heat system, press the UP or
DOWN buttons until the set temperature is 10
degrees below room temperature. The unit should
energize the strip heaters and the fan will be
running.
2-PIPE, CHANGEOVER SENSOR, WITH STRIP HEAT
STEP #4
TEST OPERATION
Page 9
Turn the power on to the Fan Coil Unit and confirm
that the thermostat is programmed correctly in setup
steps #3 and #4 on page 11 of the Owner’s Manual.

Other manuals for Johnson Controls T701DFN-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls T701DFN-1 and is the answer not in the manual?

Johnson Controls T701DFN-1 Specifications

General IconGeneral
BrandJohnson Controls
ModelT701DFN-1
CategoryThermostat
LanguageEnglish

Related product manuals