T9600
P/N 24-11447-00004 Rev. B Issue Date: 11 2020
English
USER SETTING
Press
and
button for 5 seconds at power off mode to get in parameter list. Press to scroll forward and M button to scroll backward in
the list and use
and
button to change parameter value. For T9603-T000-1JF0, press and hold for 3 seconds to access the parameter
list and press to scroll foward through the list.
PARAMETER SETTING (PART 1/2)
Code
T9600-
TF20-
1JS0
T9603-
T000-
1JF0
T9601-
TF20-
1JS0
T9600-
TF21-
1JS0 Parameter name Default Function
02
MAC (Modbus) 01
Mac address for Modbus
1-96
04
MUTE 00
Enable/disable the beep when push touch button:
00: Disable
01: Enable
05
OFFSET
0°C/
0°F
Offset to be compensate the room temperature:
Step: 0.5°C (1°F)”
Range: 5°C~-5°C (9°F- -9°F)
06
UNOCC-CLG-SP
26°C/
79°F
Cooling setpoint unoccupied mode.
Not available for Boiler application
Step: 0.5°C (1°F)
Range: 22°C~32°C (72°F-90°F)
07
UNOCC-HTG-SP
18°C/
64°F
Heating setpoint unoccupied mode.
Step: 0.5°C (1°F)
Range: 10°C~21°C (50°F-70°F)
08
SMPL-TM 10 s
Sample time,
PID parameter, only for PID
Range: 1~99 s
09
PB 5
Proportion band,
PID parameter, only for PID
Range: 1~10
10
KI 10
Integration parameter,
PID parameter, only for PID
Range: 0~99
11
BL-TIMER 30
Backlight timer.
Range: 0~99 s
12
PWR-F-RSTT 02
Restart after power failure:
00: OFF
01: ON
02: Recovery
13
TIO2ESP-CTL 00
TIO2ESP control:
00: Automatic
01: Manual
For TIO2ESP application
15
BAUD_MODBUS 00
Baud rate for Modbus:
00: 9600
01: 4800
...Continued...
INSTRUCTIONS
On/Off Setting: Press to turn on, press again to turn off, close the fan and valve.
Mode Selection: Press M to change the working mode, for cooling, for heating, for venting, for auto cooling or
heating mode. is available only for 4-pipe application or 2-pipe application when BI-FUNCTION is Change Over Sensor
input.
Temperature Setting: Press either or button to increase or decrease the temperature by 0.5°C/1°F.
Fan Speed Adjustment: Press to switch the fan mode, auto ash, high , medium , low fan.
Note: Fan stops at Floor Heating Mode, until FH-FAN parameter set to enable, for single stage oor heating application only.
Delay On/Off setup: Press and hold button 5 seconds, then “ON” appears, press button to switch On or Off delay,
then press or to adjust the minute by 30 minutes.
Note: Time-On/Off setting performs only once within one day.
Delay On/Off Cancel: Press and hold button 5 seconds, then “ON” appears, press button to switch to check On or Off
delay time, then press or adjust the time to “00:00”.
Lock setup: If Lock function is enabled, the thermostat locks automatically after 30 seconds unused.
Unlock function: Press and hold the button 5 seconds to unlock. T9603-T000-1JF0 has no button, press and hold the
button 5 seconds to unlock instead.
Tio2/ESP Manual: When Tio2/ESP function is set to Manual, press button once, to switch Tio2/ESP On or Off.