TEC2101-3 N2 Networked Single-Stage Thermostat Installation Instructions 9
Frost pr Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat.
Default: off
(on): Enabled
(off): Disabled
Heat max
2
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Cool min
2
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°/12.0°C
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
Anticycl Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling.
Default: 2.0 min
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Heat cph Sets the maximum number of
Heating cycles per hour.
Default: 4.0
Range: 3.0 to 8.0 cycles per hour
Cool cph Sets the maximum number of
Cooling cycles per hour.
Default: 4.0
Range: 3.0 or 4.0 cycles per hour
Deadband Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
increments
Fan cont Determines how the fan is activated
in response to a call for heating.
Fan cont applies to W1 and Fan
Mode auto only. Fan cont does not
affect fan operation on a call for
cooling (Y1).
Default: on
(off): The thermostat does not activate the fan in response to a call
for heating. The fan is activated by the equipment fan and limit
control.
(on): Enables the thermostat to control the fan.
Fan del Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default: off
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
Com addr N2 network address at the
thermostat; coincides with the
address assigned at the supervisory
controller.
Default: 4
Range: 1 to
255
Table 2: Installer Configuration Menu (Part 2 of 3)
Parameter
Appearing
on Display
Description and Default Selection Options