Unoccupied Timer Disable
It might be preferable for the local area to stay out of
Unoccupied mode and always stay at the Stand-By
occupancy level when no activity is present. In
instances when areas always need to be in Stand-By
mode, ready to respond to demand at any given point
in time, we recommend disabling the Unoccupied timer.
When the local PIR occupancy routine is running at the
thermostat controller, the zone drifts into Unoccupied
mode when the Unoccupied timer is set above its
factory default value of 0.0 hours.
For more information on occupancy sensor operation,
refer to the TEC2x45-4, TEC2xx6(H)-4,
TEC2xx6H-4+PIR, and TEC2xx7-4 Series Thermostat
Controllers Application Note (LIT-12011594).
Occupied
Stand-By
Unoccupied
Stand-By
= 2 Hours
Unoccupied Time
= 6 Hours
Time
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Stand-By
= 2 Hrs
Unoccupied Time
= 6 Hours
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Time
Unoccupied Time Elapsed
= Unoccupied Mode
FIG:unocc6sb2
First Movement
Detected
by PIR Device
First Movement
Detected by PIR Device
Figure 13: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours
Occupied
Stand-By
Unoccupied
Stand-By
= 2 Hrs
Unoccupied Time
= 0 Hours
Time
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time
= 0 Hours
Last Movement Detected
by PIR Device
Stand-By Time Elapsed
= Stand-By Mode
Time
FIG:unocc0sb2
First Movement Detected
by PIR Device
Stand-By
= 2 Hrs
First Movement Detected
by PIR Device
Figure 14: Unoccupied Timer Set to 0 Hours and Stand-By Timer Set to 2 Hours