TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
14
Configuring Automatic Fan Speed
Use the Fan Menu parameter in the Installer
Configuration menu to set the available Fan Mode
options. Use the FAN key to select the desired Fan
Mode option.
When selection option (2): Low-Med-High-Auto is
chosen in the Fan Menu parameter, the fan operates
as shown in Figure 21. When selection option
(3): Low-High-Auto is chosen in the Fan Menu
parameter, the fan operates at only the low and high
settings, ignoring the medium setting (Figure 21). This
operation applies to the occupied mode when the fan is
set to Auto.
Figure 20: Heating/Cooling with Reheat, Four-Pipe Applications
Temperature Increase
(Increments of 1 F/0.5 C)
oo
Heating Setpoint
Device
Closed
Device
Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
h
t
_
r
h
t
_
4
p
p
s
On/Off, Floating,
or Proportional
Outputs
Heating Output
Cooling output
Off
Off
On
On
Figure 21: Low-Med-High-Auto and Low-High-Auto Fan Operation
Temperature Deviation from Setpoint, F°
2.0F°/1.0C° to
5.0F°/2.5C°
Deadband
100%
0%
2.5
2.5
2.0 2.0
1.5
1.50.5 0.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
Heating
Cooling
Setpoint
High
FIG:fn_oprtn
Fan
Speed
The fan is off
between the
heating and
cooling setpoints
if the
parameter is
set to .
Auto Fan
AS AD