TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
12
Table 3: Control Sequences for 2-Pipe Applications
Sequence Control
Curves
Terminals Used (See Table 1.)
On/Off
Control
Floating
Control
Proportional
Control
0 = Cooling Only See Figure 15. #10 NO Cool
#11 NC Cool
#10 Open Cool
#11 Close Cool
#10 Proportional Cool
1 = Heating Only See Figure 16. #10 NO Heat
#11 NC Heat
#10 Open Heat
#11 Close Heat
#10 Proportional Heat
2 = Cooling with Reheat See Figure 17. #6 and #7 Reheat
#10 NO Cool
#11 NC Cool
#6 and #7 Reheat
#10 Open Cool
#11 Close Cool
#6 and #7 Reheat
#10 Proportional Cool
3 = Heating with Reheat See Figure 18. #6 and #7 Reheat
#10 NO Heat
#11 NC Heat
#6 and #7 Reheat
#10 Open Heat
#11 Close Heat
#6 and #7 Reheat
#10 Proportional Heat
Table 4: Control Sequences for 4-Pipe Applications
Sequence Control
Curves
Terminals Used (See Figure 6.)
On/Off
Control
Floating
Control
Proportional
Control
0 = Cooling Only See Figure 15. #10 NO Cool
#11 NC Cool
#10 Open Cool
#11 Close Cool
#10 Proportional Cool
1 = Heating Only See Figure 16. #10 NO Heat
#11 NC Heat
#10 Open Heat
#11 Close Heat
#9 Proportional Heat
2 = Cooling with
Reheat
See Figure 17. #6 and #7 Reheat
#10 NO Cool
#11 NC Cool
#6 and #7 Reheat
#10 Open Cool
#11 Close Cool
#6 and #7 Reheat
#10 Proportional Cool
3 = Heating with
Reheat
See Figure 18. #6 and #7 Reheat
#10 NO Heat
#11 NC Heat
#6 and #7 Reheat
#10 Open Heat
#11 Close Heat
#6 and #7 Reheat
#9 Proportional Heat
4 = Cooling/Heating
Four Pipes
See Figure 19. #8 NO Cool
#9 NC Cool
#10 NO Heat
#11 NC Heat
#8 Open Cool
#9 Close Cool
#10 Open Heat
#11 Close Heat
#9 Proportional Heat
#10 Proportional Cool
5 = Cooling/Heating
with Reheat,
Four Pipes
See Figure 20. #6 and #7 Reheat
#8 NO Cool
#9 NC Cool
#10 NO Heat
#11 NC Heat
#6 and #7 Reheat
#8 Open Cool
#9 Close Cool
#10 Open Heat
#11 Close Heat
#6 and #7 Reheat
#9 Proportional Heat
#10 Proportional Cool