5. Press Htg/Clg Device Type and select On-Off or Floating. Changing this option reboots the
controller in order to apply the change.
6. Press Save and the back arrow to return to the previous screen.
When in Floating mode, the Actuator Stroke Time must also be set to match the equipment. To set
the actuator stroke time:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press General.
5. Press Actuator Stroke Time and adjust accordingly.
6. Press Save and the back arrow to return to the previous screen.
Configuring the supply fan - fan coil only
About this task:
Two-pipe or four-pipe fan coil units support three different types of supply fans: single-speed fans,
multi-speed fans (up to three discrete speeds), and VSF using a 0 to 10 V control signal and an
optional binary on/off command. Note that fan control is not available when in VAV mode. To select
the fan type:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press Supply Fan.
5. Press Supply Fan Type and select Single Speed, Multi-Speed, or Variable Speed.
6. Press Save and the back arrow to return to the previous screen.
For multi-speed fan control, you can adjust the point when the medium or high speed turns on. The
fan speed is based on the load of the cooling/heating device, and is a percentage between 0 and
100. By default, the Med Speed On Cmd is 33% and the High Speed On Cmd is 66%. When only two
fan speeds are used, you must set the High Speed On Cmd to 100% to disable the third speed. To
adjust these values:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press Supply Fan.
5. Press Medium Speed On Cmd and adjust accordingly.
6. Press High Speed On Cmd and adjust accordingly.
7. Press Save and the back arrow to return to the previous screen.
TEC3000 Series On/Off or Floating Fan Coil Thermostats Installation Guide28

Other manuals for Johnson Controls TEC3330-1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TEC3330-1 Series and is the answer not in the manual?

Johnson Controls TEC3330-1 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3330-1 Series
CategoryThermostat
LanguageEnglish

Related product manuals