The following Fan Mode options are provided for multi-speed fans:
Low—Fan is continuously on low
Medium—Fan is continuously on medium
High—Fan is continuously on high
Auto—Fan cycles on demand with the controller entering cooling, heating, or dehumidification
modes
Smart—Fan cycles on demand with the controller entering cooling or heating modes during
unoccupied periods but is continuously running during occupied and standby periods
The Fan Override icon on the home screen is dependent on the fan type. The following options are
provided for single- and variable-speed fans:
On—Overrides the fan to be continuously on
Auto—Follows the behavior set as Fan Mode
Quiet—Follows the behavior set as Fan Mode, but prevents the fan from ever going above
minimum speed. The Quiet option has no effect on equipment with single-speed fans.
The following Fan Override options are provided for multi-speed fans:
Low—Fan is continuously on low
Medium—Fan is continuously on medium
High—Fan is continuously on high
Auto—Follows the behavior set as Fan Mode
Quiet—Follows the behavior set as Fan Mode, but prevents the fan from ever going above
minimum speed
To set the Fan Mode:
1. Press the Menu icon.
2. Press Setup.
3. Press General Control Setup.
4. Press Fan Mode and select On, Auto, or Smart.
5. Press Save and the back arrow to return to the previous screen.
Configuring the zone space or equipment size - units
configured with floating actuators, multi-speed fans, and
variable-speed fans only
About this task:
With non-binary outputs, the TEC3000 is configured by default to have a slower temperature
response for larger zones with normal-sized equipment. In installations with small zones and over-
sized equipment, set the Equipment Size parameter to Oversized.
To set the Equipment Size parameter:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
TEC3000 Series On/Off or Floating Fan Coil Thermostats Installation Guide30

Other manuals for Johnson Controls TEC3330-1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TEC3330-1 Series and is the answer not in the manual?

Johnson Controls TEC3330-1 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3330-1 Series
CategoryThermostat
LanguageEnglish

Related product manuals