Size
Housing
PN IN Cint
Load-shunt Max.
charging
currentR Type
400V kW A uF Ω – A
21 R 45 90 4950 5.0 – –
22 R 55 115 4950 5.0 – –
23 R 75 150 6350 5.0 – –
24 R 90 180 8400 5.0 – –
23 U 75 150 6350 5.0 – –
24 U 90 180 8400 5.0 – –
25 U 110 210 9900 2.5 – –
26 U 132 250 11700 2.5 – –
27 U 160 300 14100 2.5 – –
28 P 200 370 16200 5.8 – –
29 P 250 460 19800 5.8 – –
30 P 315 570 19800 5.8 – –
32 P (M+S) 400 710 39600 2.9 – –
33 P (M+S) 450 800 39600 2.9 – –
34 P (M+S) 500 890 39600 2.9 – –
35 P (M+S) 560 1000 39600 2.9 – –
36 P (M+S+S) 630 1150 59400 1.9 – –
Legend
P
N Rated power
I
N Rated current
C
int Real capacity
Table 19: Technical data of COMBIVERT drive converters
NOTICE
A restart for AIC with NTC is allowed only after 5 minutes.
60
DIMENSIONING